Control panel labels for panel shops and OEMs
Engraved control panel labels for UL 508A nameplates, SCCR, disconnects and device IDs. Load your nameplate schedule, get a proof.
Open the builderBulk quote / send a list
Have a schedule or spreadsheet? Email it to sales@llamacoids.ca and we'll quote the whole job.
Control panel labels are the engraved plates on and inside an industrial control panel: the main nameplate (voltage, full-load current, SCCR and the rest of the listing data), disconnect purpose tags, device IDs that match the drawings, and legend plates on the operators. We laser engrave them in acrylic two-color laminate from your schedule or BOM.
What labels does a control panel need?
A control panel needs a main nameplate, disconnect and multi-source markings, device and terminal IDs that match the drawings, operator legend plates, and any required warnings such as arc flash or multiple power sources.
This page is about industrial control panels (UL 508A / NEC Article 409) and machine panels (NFPA 79). For panelboards and switchboards in buildings, see electrical panel labels. Homeowners looking for a residential directory should use breaker box labels.
| Label | What it carries | Typical source | Where it goes |
|---|---|---|---|
| Main nameplate | Manufacturer ID, supply V/ph/Hz, FLC, SCCR at max V, enclosure Type, drawing index; service-equipment wording only if built for it | UL 508A markings + NEC 409.110 | On the enclosure, plainly visible after install (supply data outside per 2023 NEC 409.110) |
| Machine nameplate (machinery) | Supplier, model/serial, V/ph/Hz, FLC, largest load, protective-device rating where provided, panel SCCR, drawing nos. | NFPA 79 16.4 (verify the edition your AHJ adopted) | Outside the enclosure or on the machine next to it |
| Disconnect purpose | What it feeds / which source | NEC 110.22(A); multi-source notes on the nameplate | At each disconnecting means |
| Device / component IDs | Tag that matches the schematic (FU1, KM1, PB1) | Drawing device schedule | On or next to the device / backpan |
| Operator legend plates | START, STOP, HAND-OFF-AUTO, E-STOP | Customer standard / NFPA 79 operator marking practice | Behind 22 / 30 mm operators. See legend plates |
| Arc flash / hazard | Study data or required warning | NEC 110.16 / project. See arc flash labels | Per study / AHJ |
Send the schedule to sales@llamacoids.ca and we'll quote the full set, or load it in the builder yourself.
UL 508A nameplate fields (SCCR, max voltage, and related markings)
The main industrial control panel nameplate has to carry the listing data the AHJ and the Follow-Up inspector expect, including the short-circuit current rating and the maximum voltage that rating applies at.
In plain language, the plate usually carries:
- Manufacturer name, trademark or file number
- Supply voltage, phase, frequency and full-load current for each incoming supply
- Short-circuit current rating (SCCR) with the maximum voltage that rating applies at
- Industrial control panel designation
- Enclosure Type
- Wiring-diagram or drawing index
- "Suitable for use as service equipment" only when the construction backs it
- Multi-source disconnect notes when more than one disconnect is required to de-energize
UL 508A Supplement SB5.1 is the usual reference for putting SCCR and maximum voltage on the nameplate. Where a high-fault rating depends on a field-installed branch-circuit or feeder protective device, the standard also expects that device type and size to appear on the marking (SB5.1.2 / SB5.1.3 territory; confirm against the edition your shop works to). NEC 409.110 is the installation-code twin: permanent markings visible after install, with supply voltage/phase/frequency/FLC and any multi-source disconnect note attached to the outside of the enclosure under the 2023 NEC.
Check the edition your AHJ adopted. We engrave the data you send. We do not calculate SCCR or issue the UL mark.
| Field | Example (fictional shop data) |
|---|---|
| Manufacturer | ACME PANEL CO. |
| Designation | ICP-12 / DWG E-401 |
| Enclosure Type | TYPE 12 |
| Supply | 480 V 3Ø 60 Hz |
| FLC | FLC ______ A |
| SCCR | SCCR: ______ kA RMS SYM. AT ______ V |
| Drawing no. | E-401 REV C |
| Serial | SN ______ |
One thing to be clear on: the UL listing mark comes from UL through your shop's listing, not from us. We engrave the identification plates. We do not supply UL labels.
The SCCR line on the nameplate
The SCCR on the plate is the panel's assembly rating: the lowest applicable power-circuit component or combination after any permitted current-limiting step. It is not the interrupting rating of the main breaker alone.
UL 508A Supplement SB walks the calculation in four steps that shops already know:
- Identify power-circuit components in each branch (SB4.2).
- Read marked ratings or use the default table where the standard allows (Table SB4.1). Do not invent default kA values; use the edition you work to.
- Apply any permitted current-limiting in the feeder (SB4.3).
- Take the overall panel value (SB4.4) and mark it per SB5.1, with the maximum voltage that rating applies at.
Illustrative wording shops often put on the plate (your procedure and AHJ win): SCCR: 65 kA RMS SYM. AT 480 V. When a high-fault rating depends on a specific fuse class or size, the plate or accompanying marking has to say so. Confirm that wording against SB5.1.2 / SB5.1.3 in your edition.
This is separate from NEC 110.24 available-fault-current field marking on service equipment. That topic lives on the electrical panel labels page.
Paste the lines in the builder or email the sheet to sales@llamacoids.ca.
NFPA 79 machine nameplate
Industrial machinery gets a machine nameplate under NFPA 79 Chapter 16 in addition to, or coordinated with, any UL 508A panel nameplates on the control enclosures.
Clause 16.4 / 16.4.1 (confirm the edition your AHJ adopted; numbering can move between editions) calls for a durable nameplate on the outside of the enclosure or on the machine next to it, carrying:
- Name or trademark of the supplier
- Model, serial number or other designation
- Rated voltage, number of phases and frequency (if AC), and full-load current for each supply
- Ampere rating of the largest motor or load
- Maximum ampere rating of the short-circuit and ground-fault protective device, where provided
- Short-circuit current rating of the industrial control panel
- Electrical diagram number(s) or the index to the drawings
On a multi-panel machine, each listed industrial control panel keeps its own nameplate and SCCR. The machine nameplate and overall SCCR sit on the panel tied to the facility supply. For oversized door and machine plates, see engraved nameplates.
Disconnect marking and device IDs
Every disconnect needs a durable purpose mark unless the purpose is obvious (NEC 110.22(A)). Inside the panel, device tags should use the same designators as the schematic.
Common examples:
MAIN DISCONNECT / 480 V 3ØCONTROL POWER DISCONNECTFU1,KM3,TB-POWER
Multi-source panels need a marking that more than one disconnect is required to de-energize the equipment. That ties to NEC 409.110 practice; put the wording your listing and drawings call for.
Mounting: adhesive on clean painted steel indoors; screws or rivets on doors that get abused or outdoor Type 4/4X. Use 1/16 inch for small device tags and legend plates, and 1/8 inch for door nameplates and anything screwed or riveted. For field equipment outside the enclosure, see equipment tags.
Read the transcript
This is the label builder on Lamacoids USA. Type the tag, pick a size and color, and see it at true size before you order. Line one is the name from the drawings: PANEL EM-1. Line two is the details: 120/208 volt, three phase, four wire. Set 3/8 inch letters and the plate grows to fit. It's an emergency panel, so white on red, 1/8 inch thick. Under finish, pick adhesive back or screw holes. This one gets screws, so holes on, adhesive off. Set the quantity and add it to the list. Nothing is charged here. You get a quote and a PDF proof by email first. Build the rest of the job the same way, or load your panel schedule from a spreadsheet.
How to spec engraved labels on the drawing and BOM
Put every plate on a nameplate schedule, call it out by tag number on the layout, and point the BOM at that schedule. Do not bury legends in a Word file that never makes it into the drawing package.
Required schedule columns (one row per plate):
- Tag number (PB1, DS1, NP-07)
- Legend text line by line, exactly as engraved, including punctuation
- Size (W × H in inches)
- Colors (for example white on black; black on yellow for E-STOP)
- Mounting (adhesive vs hole count/diameter)
- Quantity per panel
- Optional: device the plate belongs to
On the layout, use a tag balloon only. Do not retype the legend on the layout drawing. Add a general note block for material, default thickness/color and "schedule governs." Put a BOM line that references the schedule sheet, revision and tag list.
Letter height: keep text readable from arm's length. On a 1 inch plate, two lines at about 3/16 inch or one line at 3/8 inch are practical. Text below 1/8 inch is hard to read in a dim enclosure. The builder shows text height on every line and flags rows that will not fit.
Common failure modes we see on reorders: symbols lost in CAD export, mixed case on units (480V vs 480 V), schedule/layout tag mismatch, and legends stuck in a separate email thread instead of the drawing package.
| Tag | Legend (line by line) | Size | Colors | Mount | Qty |
|---|---|---|---|---|---|
| PB1 | START | 22 mm legend | Black on white | Operator hole | 1 |
| PB2 | STOP | 22 mm legend | Black on white | Operator hole | 1 |
| SS1 | HAND OFF AUTO | 22 mm legend | Black on white | Operator hole | 1 |
| PL1 | RUN | 22 mm legend | White on black | Operator hole | 1 |
| DS1 | MAIN DISCONNECT 480 V 3Ø | 1 x 3 in | White on black | Adhesive | 1 |
| ES1 | EMERGENCY STOP | 30 mm legend | Black on yellow | Operator hole | 1 |
Email the XLSX/CSV or a PDF of the drawing schedule to sales@llamacoids.ca, or load it with spreadsheet import.
Ordering a labeled kit for a panel build
Order one labeled kit per panel, with plates marked to the same tag numbers as the drawing, so the assembler mounts without sorting a mixed pile.
Load the schedule in the builder (or send a job file the way panel shops already do for legend plates). Add spares as a separate BOM line. We ship labeled and listed on one proof so every plate matches the schedule row before it leaves the shop. Same-day turnaround is available when the proof is approved in time.
Engraved laminate vs printed vinyl on a control panel
Printed vinyl is fine for many indoor IDs. Engraved acrylic two-color laminate is what most Division 26 and machine specs mean by "engraved laminated plastic nameplates," and it holds up better to door rub and washdown. The letters are cut into the plate, so there is no ink on the surface to smear and no film edge to lift.
When the spec names engraved plates, send the schedule here. Read more about the material on what a lamacoid is. See how pricing works for how the builder prices each plate by area and thickness.
Timely notes
Mounting surface and adhesive
Recent guidance from industrial label suppliers stresses matching adhesive and stock to the mounting-surface temperature, and keeping identifiers consistent with the drawings. We agree: match the adhesive or fastener to the surface, keep tag numbers identical to the schematic, and approve a sample when the surface is unusual. When the spec calls for engraved acrylic plates, send the schedule here.
UL Canada certification change (effective 2026-10-01)
UL lists a certification-requirement change for industrial control panels certified for Canada, effective 2026-10-01. Shops shipping panels into Canada should confirm the current CSA path with their NRTL. We still engrave the nameplate data either way. We do not certify panels. Canadian orders go through Llamacoids in Canada.
Common questions
What labels does an industrial control panel need?
A main nameplate with listing data (including SCCR), disconnect purpose marks, device and terminal IDs that match the drawings, operator legend plates, and any required warnings such as arc flash or multiple power sources.
What information goes on a UL 508A control panel nameplate?
Manufacturer ID, supply voltage, phase, frequency, full-load current, SCCR at the maximum voltage that rating applies at, enclosure Type, drawing index, and service-equipment or multi-source notes when they apply. We engrave the data you send. We do not calculate SCCR or issue the UL mark.
How is the SCCR shown on the nameplate?
As the panel's assembly short-circuit current rating in kA rms symmetrical, with the maximum voltage that rating applies at, per UL 508A Supplement SB5.1. An illustrative form is SCCR: 65 kA RMS SYM. AT 480 V. Your shop procedure and AHJ govern the exact string.
What does NFPA 79 require on a machine nameplate?
Clause 16.4 calls for supplier, model/serial, rated V/ph/Hz and FLC per supply, largest motor or load ampere rating, protective-device rating where provided, panel SCCR, and electrical diagram numbers. Check the edition your AHJ adopted.
Can you engrave a full set from our nameplate schedule or BOM?
Yes. Load an Excel or CSV schedule in the builder and map the columns, or email the schedule to sales@llamacoids.ca. Every row becomes a plate on one proof.
Do you supply the UL listing mark?
No. The UL listing mark comes from UL through your shop's listing. We engrave the identification plates, legend plates and nameplates. We do not supply UL labels.
What is the difference between a control panel nameplate and a legend plate?
The nameplate carries the panel's listing and supply data (voltage, FLC, SCCR and related fields). A legend plate is the small operator label behind a 22 mm or 30 mm push button, selector or pilot light, such as START or E-STOP.
Engraved or printed: which should I use inside a control panel?
Printed vinyl is fine for many indoor IDs. Use engraved acrylic two-color laminate when the spec calls for engraved laminated plastic nameplates, or when plates see door rub, washdown or long service life.
Open the builder, or email your nameplate schedule to sales@llamacoids.ca. Call +1 289-275-9572. Llamacoids Inc, 1550 Yorkton Court, Burlington ON.
Building panels in Canada? Order from Llamacoids in Canada.
Related products
- Electrical panel labels (panelboards / switchboards / building disconnects)
- Legend plates (22 mm and 30 mm pushbutton legends)
- Engraved nameplates
- Equipment tags
- Arc flash labels
- What a lamacoid is
- Breaker box labels
- Label builder / spreadsheet import
- Pricing
- Contact and bulk quotes
Code and standard references on this page cite NEC 2023 (NFPA 70), UL 508A Supplement SB (secondary sources: Rockwell SCCR-AT002 and related industry summaries) and NFPA 79 clause 16.4 (Lewis Bass / UL Solutions summaries), reviewed on 2026-10-29. Primary UL/NFPA PDFs were not re-read for this page; confirm exact wording against the edition your AHJ and NRTL require. Local amendments apply. Your inspector and engineer of record have the final say.